Eagle Instruction Manual Appendix H: Eagle Transformer Gas Tester Model 73
NOTE: The EAGLE can be calibrated either with or without the
dilution fitting in place. If calibrated without the dilution
fitting in place, then display readings must be doubled to
determine the actual gas concentration. If calibrated with the
dilution fitting in place, then the sample bag must be used
during calibration, and the display readings will be the actual
gas concentrations.
CAUTION:If the dilution fitting is in place for calibration, do not use a
demand flow regulator. Use a sample bag. The use of a demand
flow regulator with a dilution fitting when calibrating will
result in an inaccurate calibration.
Alarms
All the gas alarms on the Transformer Gas Tester are set to OFF.
Table 17: Parts List: Eagle Tank Tester Model
Part Number Description
80-0405RK Dilution fitting (1:1)
81-1126RK Sample bag, 9” x 9”, tedlar